Specifications The output voltage Measurement range Insulation test 250V(0%~+20%) 0.01MΩ~250MΩ+/-(3%+5) 500V(0%~+20%) 0.01MΩ~500MΩ+/-(3%+5) 1000V(0%~+20%) 0.01MΩ~1000MΩ+/-(3%+5) 1.00MΩ~5.00MΩ+/-(5%+0.1GΩ ) 5.00MΩ~10.00MΩ+/-(10%+0.) 2500V(0%~+20%) 0.1MΩ~2.00GΩ+/-(3%+5) 2.00GΩ~20.00GΩ+/-(5%+0.2GΩ ) 20.00GΩ~100.0GΩ+/-(10%+2GΩ ) Short-circuit current 2mA Functions of multimeter DC voltage measurement 0.1~1000V+/-0.5% AC voltage measurement 0.1~750V+/-1% Continuity test
Power 6x1.5V AA batteries Overall dimensions 180mm x 140mm x 65mm Weight Approximately 950g Security Level CE ETL CAT III 1000V.CATIV600V |